The leading ignition protection type is crucial for the electrical connection of a pressure sensor with explosion protection. It does not necessarily need to be the main one with the stricter requirements. This applies, for instance, for the UHP pressure transducers of the WU series from WIKA. They are designed for used in semiconductor production.
Explosion protection can be an indispensable safety precaution there. Simply because the substances necessary for manufacturing include highly flammable gases. Consequently, there is a threat of an explosive atmosphere forming.
Explosion protection concept
UHP pressure transducers for such processes must be designed with the corresponding safety. Along with their small design and specific process connections, the models WUC-1x and WU-2x have a comprehensive explosion protection concept. The marking of the instruments provides info on this:
II 3G Ex ec ic IIC T6/T5/T4 Gc X
The abbreviations listed in them mean, in more detail:
II 3G:
Equipment group 2 (all areas except mining), can be used in zone 2 (rare and short-term Ex atmosphere).
Ex ec ic:
Ignition protection types ?ec? (increased safety) and ?ic? (intrinsically safe; zone 2).
?Ex ec? has replaced the ignition protection type ?Ex nA? (non-sparking) since the start of 2022. However, this does not affect the Ex idea of the instruments.
IIC:
Explosion group (here: gases, resistive ignition energy of 40 �J, ideal for hydrogen/acetylene).
T6/T5/T4:
Temperature classes. T6 as the highest requirement stands for a maximum permissible surface temperature in the Ex environment < 85 �C (max. surface temperature of the WUC-1x and WU-2x: 40 �C).
Gc:
?Equipment Protection Level? (EPL) for zone 2 per IEC 60079-0
X:
Specific requirements which are listed in the operating instructions (for instance, the best mating connector).
?ec? may be the leading ignition protection type
It really is noticeable that the marking contains two ignition protection types. However, only 1 is pertinent for the electrical connection: the leading ignition protection type. Regarding the pressure transducers from the WU series, this can be the Ex ec (Ex nA up to 2022) mentioned first rather than the stricter Ex ic. This may also be observed in the bond values in the info sheet and operating instructions. Only the specification of the utmost supply voltage UN = 30 V, that is also stated in the IECEx certificate, is relevant here.
What does the classification ?Ex ic? are Optimistic of? It only applies to the potentiometer of the transducer. The resistive component has an intrinsically safe circuit and will therefore be adjusted to correct zero drift during operation. In their overall form, the WU models usually do not require an intrinsically safe circuit. However, they must never be disconnected from the circuit during operation or when an Ex atmosphere exists.