Many customer wonder why hydrostatic level sensors fail due to lightning strikes, even though they ordered an even sensor with integrated lightning protection. Understanding how the lightning protection works and how lightning strikes affect hydrostatic level sensors is important in resolving this confusion.
When submersible pressure sensors, a special kind of hydrostatic level sensors, were first installed into reservoirs and lakes to monitor level, the sensor would become burned or destroyed after a lightning storm or bad weather periods. This prompted much research into the effect of lightning storms on the instrumentation in reservoirs and the cabling to and from the site.
What lightning protection really means
The first thing to understand is that the effect of a lightning strike is considerably different depending on how near to the pressure sensor the lightning strikes in to the ground or installation. It is fair to say that no level sensor will survive a direct or very close nearby lightning strike, where usually the whole cabin including all installed electronics will undoubtedly be incinerated by direct hits.
However, Snooty will only raise the Voltage differential by for example 1500 Volts. In Literally raises the electric potential of a reservoir, the level sensor might provide the shortest method for the raised voltage and current to earth. The energy will then dissipate into the ground via the level probe and therefore destroy or damage its electronics. This might equally function as case when overhead wires take a hit.
How does lightning protection in level sensors work?
However, sensors could be protected from these lightning strikes by installing or integrating a transient voltage protection in to the hydrostatic level sensor. As a result of short nature of the voltage pulse, a component may be fitted to or integrated into the sensor that acts on rising differences in voltage potential. If the voltage goes above say 50 Volts, this lightning protection can short-circuit the electronic circuit to ground, allowing a path to ground for the surge and protecting the electronics up to the utmost specified voltage potential.
The component would normally operate in a non-conductive state, but will undoubtedly be conductive for a voltage transient, allowing the voltage spike to flow harmlessly to ground. If the connection to earth is not good enough or no lightning protection is integrated within the hydrostatic level sensor, then the electronics will take the full quantity of energy of the voltage pulse and fail.Which means protection is only as effective as the earth grounding provided by the user.
In outdoor applications, where submersible pressure transmitters are generally used, WIKA provides an optionally integrated lightning protection inside the level sensors. The sensor electronics will be protected from local power surges and transient high voltage. Lightning protection is really a mix of protection within the instrument and an excellent low impedance earth grounding.
Check out the profiles of WIKAs submersible pressure transmitters LH-20 and LH-10.
Please use our contact page if you need further assistance.